Waste Heat
Click the individual drawing to magnify
|
Front Elevation |
Side Elevation |
 |
 |
PLEASE ADVISE
SIDE OF DOOR TO BE HINGED AND WHICH SIDE MOUNTINGS TO BE LOCATED. ALLOW 300Omm
AT FRONT OR REAR OF BOILER FOR TUBE REMOVAL.
All
dimensions and relevant connections are in mm
|
MODEL
STEAM Kg/h, Hot water kW
|
WH
0.5 227 150
|
WH
1.5 714 450
|
WH
3 1361 900
|
WH
3.5 1600 1050
|
WH
5 2268 1500
|
WH
7 3200 2100
|
WH
8 3628
2400
|
WH
10 4536 3000
|
|
A
|
1500
|
1500
|
1700
|
1700
|
2000
|
2300
|
2300
|
2650
|
|
B
|
3850
|
3990
|
4900
|
5150
|
5150
|
5500
|
5500
|
5800
|
|
C
|
1450
|
1570
|
1650
|
1650
|
1950
|
2230
|
2230
|
2530
|
|
D
|
800
|
900
|
1100
|
1100
|
1400
|
1700
|
1700
|
2050
|
|
E
|
400
|
500
|
600
|
600
|
750
|
900
|
900
|
1000
|
|
F
|
250
|
500
|
600
|
600
|
600
|
600
|
600
|
600
|
|
G
|
2050
|
1590
|
1800
|
1800
|
1800
|
1800
|
1800
|
2000
|
|
H
|
400
|
400
|
600
|
600
|
650
|
650
|
650
|
700
|
|
D1
|
SIZE
TO SUIT YOUR DUCTING
|
|
D2
|
300
|
400
|
400
|
400
|
500
|
600
|
600
|
600
|
|
DRY WEIGHT
K9
|
2700
|
4200
|
4800
|
6000
|
7200
|
8700
|
10100
|
11400
|
For Steam Boilers add 40Omm to width dimension W either left or right
depending on position of mountings
Specification
A range of well proven highly efficient Boilers for Steam
and Hot Water Applications.
Standard Units Single Pass with inlet duct at front of
Boiler sized to suit customers requirements and outlet Duct fitted at rear. Two
Pass Design offered if required with inlet and outlet Ducts both fitted front of
boiler.
Waste Heat Hot Water Boilers are supplied complete with
Flanged flow & Return Connections. All Controls supplied to Client's
specification.
Waste Heat Steam Boilers are supplied with
 | High-lift
Safety Valve
|
 |
Stop Valve
|
 |
Feed Check and
Anti-syphon Valve
|
 |
Blow Down
Valve
|
 |
Pressure Gauge
|
 |
Vent Cock
|
 |
Water Gauge
Sets with Protectors
|
 |
Self
Monitoring Water level Controls
|
 |
TDS System
|
 |
Water Sample
Cooler
|
 |
Feed Pump
|
 |
Pressure
Switches
|
 |
Wiring to
Junction Box
|
A.0.T.C. Panel not
included as standard but can also be supplied as an extra.
ADDITIONAL EQUIPMENT
OXIDISERS, STEAM
DRUMS, BUFFER TANKS AND OTHER ANCILLARY EQUIPMENT TO SUIT INDIVIDUAL CUSTOMER
REQUIREMENTS - DETAILS ON REQUEST.
Custom built
models on request.
|