Hoval Logo Corgi Safe Contractor

Technical Spec

Home
Back

Dragon Shell

Click the individual drawing to magnify   

Front Elevation

Isometric View

Side Elevation

SPECIFICATION S.1

Boiler tappings are one-off flanged flow and return connections and eight tappings which are fitted on top of the boiler to accommodate altitude gauge, thermometer, air vent, safety valves, limit and control thermostats. A drain cock is mounted at the rear of the boiler. A control high limit dual thermostat is supplied as standard pre-wired and a short flexible oil connection and strainer. An Electronic temperature controller, combining operating and limit function complete with type K Thermo couple located in common flow header can be supplied as an optional extra.

SPECIFICATION S.2

This boiler burner unit is fully packaged, all as S.1, but includes mountings and meets Ministry specifications, with particular reference to M & E 3. Thermostats are supplied as standard, pre‑wired together with short flexible oil connection and strainer. Packaged unit includes boilers with fully insulated casings up to 100mm and/or to the relevant British Standard. Boiler tappings are one-off flanged flow and return connections and eight tappings with fitted altitude gauge, safety valve (National enclosed spring loaded type), control and limit dual thermostat in pocket, open air vent, spare tapping for high/low thermostat. In addition a drain cock is mounted at the rear of the boiler.

SPECIFICATION S.4

Boiler only otherwise all as S. 1, supplied with boiler casing and front plate to suit burners being supplied by customer.

SPECIFICATION S.5

Comprehensive boiler to any of above specifications complete with circulating pump or shunt pump and all interconnecting pipe work, valves and fittings. Details on request.

SPECIFICATION S.6

Boilers supplied to any of the above specifications as combination units complete with hot water cylinders. Details on request.

COMPACT DESIGN

The DRAGON SHELL 3 pass wet back boiler with pressurised combustion chamber is designed to allow the first and second passes of gas to be made within the chamber. The boiler is designed with a unique third pass heat exchange (Kayanson 'CONVECTION' design) to ensure a minimum of 80% efficiency.

BOILER MAINTENANCE

The oil gas burner supplied is mounted on a firing door, which is insulated together with a refractory lining and seal on the inside of the boiler. In addition, a hinged door (standard left) is provided at front of boiler for access to the third pass, together with an inspection plate at the rear of the boiler. (Right hand hinge can be supplied if required and specified).

QUALITY AND EFFICIENCY

Units, insulated to the relevant British Standards, are working under pressurised combustion overcoming light-up or cold start resistance. Each boiler is constructed from boiler quality steel plates and complies to all relevant International, British and Ministry standards. Quality has been assessed by BSI Quality Assurance Service to BS5750, certificate No. FM1566

Tables

All dimensions and relevant connections are in mm.

MODEL

D.4

D.5

D.6

D.7

D.8

D.10

Rating kW

1172

1465

1758

2052

2345

3000

A

1442

1585

1880

1880

2030

2120

B

2736

2834

3178

3178

3183

3600

c

1576

1726

2020

2020

2168

2320

D

1000

1100

1430

1430

1600

1700

E

1630

1700

1700

1700

1600

1800

F

454

550

546

546

696

1106

G

758

816

875

875

923

1040

H

275

275

275

275

275

275

j

154

219

219

219

219

219

K

971

1096

996

996

996

1413

L

300

295

300

300

300

300

m

785

800

1140

1140

1175

1175

N

558

591

686

686

656

656

Safety Valve

Sized to suit application

Vent

65

65

65

65

65

65

Drain

25

25

25

25

25

25

Flue. Die.

400

450

500

500

550

600

F and R

125

125

150

150

150

150

Hydraulic Res.

40.79

62.55

45.17

58.56

76.97

122.51

11T Diff. M/bar

 

 

 

 

 

 

Water Content

1314

1903

2200

2706

2901

3824

Litres

 

 

 

 

 

 

Std. Dry Weight kg

3270

4427

5036

6105

6270

7540

 

MODEL

D.4

D.5

D.6

D.7

D.8

D.10

Oil Rate L/hr 15.50C

137.85

172.32

206.77

241.24

275.7

344.63

Oil Line Size BSP

 

 

 

Y,

1/2

3/4'.

Burner Motor kw

2.2

3

5.5

7.5

7.5

11

Start Current Amps

25

35

40

60

60

65

Run Current Amps

4.6

6.1

11.5

14.4

14.4

25

Gas Rate M3/hr

136.19

170.24

204.29

238.34

272.4

340.48

Gas Pressure Required M/bar

37

31

34

36

46

49

Burner Motor kW

2.2

3

4

7.5

7.5

7.5

Start Current Amps

25

35

45

60

60

60

Run Current Amps

4.6

6.1

8

25

25

25

Voltage

40Ov

3PH

415v

415v

3PH

415v

415v

3PH

415v

 

3PH

3PH

3PH

D.4 - D.10 flow and return connections flanged to BS4504. Table 6/5 

D.4 - D.10 flue outlet flanged.

Home ] Back ]