SPECIFICATION S.1

Boiler tappings are one-off flanged flow and return connections and seven tappings which are fitted on the side and rear to accommodate altitude gauge, thermometer, air vent, safety valves, limit and control thermostats. A drain cock is mounted at the rear of the boiler. A control high limit dual thermostat is supplied as standard pre-wired and a short flexible oil connection and strainer. An Electronic temperature controller, combining operating and limit function complete with type K Thermo couple located in common flow header can be supplied as an optional extra.

 SPECIFICATION S.2

This boiler unit is fully packaged, all as S.1, but includes mountings and meets relevant Ministry specifications, with particular reference to M & E 3. Thermostats are supplied as standard, pre-wired together with short flexible oil connections and strainer. Packaged unit includes boilers with fully insulated casings up to 100mm and/or to the relevant British Standard. Boiler tappings are one-off flanged flow and return connections and seven tappings with fitted altitude gauge, thermometer, safety valve and control limit dual thermostat in pocket, open air vent, spare tapping for high/low thermostat.

 SPECIFICATION S.4

Boiler only otherwise all as S.1, supplied with casing and boiler front plate to suit burners being supplied by customer.

SPECIFICATION S.5

Comprehensive boiler to any of the above specifications complete with mixing shunt pump and all interconnecting pipe work, valves and fittings. Details on request.

 SPECIFICATION S.6

Boilers supplied to any of the above specifications as combination units complete with hot water cylinders. Details on request.

 COMPACT DESIGN

The EASYSTACK MODULAR 3 pass wet back boiler with pressurised combustion chamber is designed to allow the first and second passes of gas to be made within the chamber. The vertically stacked design offers obvious space saving and greater flexibility/turndown ratio. There is also  the facility to isolate individual boilers within modular arrangement.

BOILER MAINTENANCE

The oil or gas burner supplied is mounted on a firing door, which is insulated together with a refractory lining and seal on the inside of the boiler. In addition, a hinged door is provided at the front of the boiler for access to the third pass, together with an inspection plate at the rear of the boiler. Dual left/right hand opening supplied as standard.

 QUALITY AND EFFICIENCY

Units, insulated to the relevant British Standards, are working under pressurised combustion overcoming light-up or cold start resistance. Each boiler is constructed from boiler quality steel plates and complies to all the relevant International, British and Ministry standards. Quality has been assessed by BSI Quality Assurance Service to BS5750, certificate No. FM1566.

Tables

Minimum static head all models three metres. Minimum clearance: at front for burner projection; at rear for pipework only; at sides no clearance necessary. Please contact our drawing office for more specific information. All dimensions and relevant connections are in mm

MODEL

RATING kW

A

B

C

D

E

F

G

H

J

K

L

NW1

35

520

490

831

440

450

791

341

166

579

95

45

NW2

50

520

620

981

440

580

941

366

160

725

95

50

NW3

65

520

690

981

440

650

941

366

160

725

108

50

NW4

85

600

770

981

520

730

941

366

160

719

120

60

NW5

105

600

770

1081

520

730

1041

366

166

810

120

60

NW6

130

680

840

1181

600

800

1141

411

154

914

132

80

NW7

155

680

990

1181

600

950

1141

411

154

914

132

80

NW8

190

680

990

1181

600

950

1141

411

154

914

145

80

NW9

225

780

1140

1231

700

1100

1141

441

166

950

145

80

NW10

260

780

1340

1231

700

1300

1141

441

166

950

170

80

NW11

300

780

1340

1381

700

1300

1341

456

166

1097

170

80

NW12

400

780

1440

1481

700

1400

1441

516

199

1155

195

80

NW13

500

860

1570

1581

780

1530

1541

516

204

1244

195

80

NW14

600

860

1570

1581

780

1530

1541

513

206

1244

220

80

NW15

700

860

1570

1831

780

1530

1741

513

206

1494

220

80

 

 

CONNECTIONS

Hyd. Res.11° Diff mbar

WATER CONTENT LITRES

BOILER TOTAL DRY WEIGHT

GAS RATE M3/Hr. 

OIL RATE At 15.5°C Ltrs/Hr

MODEL

FLU DIA

F AND  R

DRAIN

STY VALVE

VENT

NW1

100

32

20

20

32

10.1

36

184

4.07

4.09

NW2

100

38

20

20

32

10.8

50

205

5.81

5.90

NW3

125

38

20

20

32

18.9

58

277

7.56

7.73

NW4

150

50

20

20

32

12.1

73

352

9.88

10.00

NW5

150

50

20

25

32

18.7

80

375

12.21

12.73

NW6

175

65

20

25

32

9.8

101

469

15.12

15.45

NW7

175

65

20

20

38

13.0

115

537

18.02

18.18

NW8

200

65

20

20

38

19.4

131

584

22.10

22.27

NW9

200

80

20

20

38

14.5

153

675

26.16

26.36

NW10

250

80

20

20

38

20.7

179

779

30.23

30.54

NW11

250

80

20

20

38

26.8

214

897

34.88

35.27

NW12

300

100

25

25

50

16.7

251

1047

46.51

47.00

NW13

300

100

25

32

50

25.3

301

1239

58.14

58.72

NW14

350

100

25

32

50

35.2

347

1353

69.76

70.44

NW15

350

100

2

32

65

47.7

400

1542

81.39

82.63

Gas rates are based on gross cal. value of 38.7 mj/m3

Gas pressure at inlet on all models 17.5 mbar. NW1-NW5 flow and return connections BSP. Female Sockets. NW6-NW15 flow and return connections flanged to BS.4504. Table 6/5.

All flue connections are collars to take the Spigot end of standard flue pipe.

 