Hoval Logo Corgi Safe Contractor

Technical Spec

Home
Back

Hydra Atmospheric

Click the individual drawing to magnify   

Front Elevation

Side Elevation

Rear View

Minimum clearance: at front 61Omm all models: at rear for pipe work only; at sides no clearance necessary. Please contact our drawing office for more specific information.

 SPECIFICATION S.1

Boiler body, complete with twin heat exchangers (second stage finned tube for additional surface area), down draught diverter, drain cock vent tapping, combustion cover door and enameled easing, finished Hammer Blue (BS4800) any other BS colour on request. Boiler supplied complete with gas burner, electric igniter, electronic control box, solenoid valves and drain cock. Substantially insulated up to 10Omm and/or to appropriate British Standard and Military Spec. Controls include gas governor, high limit and operating thermostat to comply to British Gas and relevant International Requirements, Electrical supply 230 volt AC single phase. Boilers can be supplied as multi-units, being separately flued. Flame failure is, by way of electric flame rectification, ignition is automatic from switch on. The shutdown of burner caused by name failure is immediate. High/low modulating controls can be supplied as an optional extra. Also available, an Electronic temperature controller, combining operating and limit function complete with type K Thermocouple located in common flow header.

SPECIFICATION S.2

All as S.1 but offered to meet relevant M & E 3 specifications with following mountings supplied: Nationally enclosed spring loaded safety valves; Altitude gauge and Thermometer.

SPECIFICATION S.5

Comprehensive boiler to any of the above specifications complete with circulating pump or shunt pump and all interconnecting pipe work, valves and fittings. Details on request.

SPECIFICATION S.6

Boilers supplied to any of the above specifications as combination units complete with hot water cylinders. Details on request.

COMPACT DESIGN

Greatly reduced height for low headroom projects. Complete range will go through standard doorway.

EASE OF MAINTENANCE

Boiler flue cleaning is from top of boiler, sweeping through unrestricted flueways. Compact design means boilers will fit into confined spaces.

QUALITY AND EFFICIENCY

Units manufactured from Boiler Quality Plate insulated to the relevant British Standard. Quality has been assessed by BSI Quality Assurance Service to BS5750, Certificate No. EM 1566. Simple flexible system is achieved, giving good turndown ratios of temperature requirements. The system can be controlled by either a step sequence control or by individual thermostats, wired into energy control management system.

MODEL

NH

200

NH

300

NH

400

NH

500

NH

600

NH

800

NH

1000

NH

1200

NH

1500

RATING kW

58

88

117

146

176

234

300

352

440

A

522

614

706

834

926

1136

1320

1524

1800

B

832

832

832

882

882

920

920

940

940

C

877

877

877

877

927

927

927

927

927

D

382

474

566

658

750

960

1144

1328

1604

E

729

739

739

719

745

745

745

745

745

F

826

826

826

826

876

876

876

876

876

G

592

585

577

577

577

522

522

522

496

H

206

206

206

206

256

256

256

256

256

J

133

170

135

135

110

115

115

140

85

K

240

260

260

260

260

340

340

390

390

M

596

596

596

596

596

596

596

596

596

N

150

150

150

150

150

150

150

150

150

Flue Diameter

175

200

250

250

300

350

350

400

450

Flow/Return

40

50

65

65

65

80

80

80

100

Drain

19

19

19

19

19

19

19

25

25

Safety Valve

20

20

20

20

20

20

25

25

25

Vent

32

32

32

32

40

40

40

50

50

Gas Connection

20

20

20

20

20

32

32

32

40

Hydraulic Res.

mbar 11°C Diff.

20.5

 

45

 

16

 

19

 

24.5

 

22

 

35

 

51

 

27

 

Min. Water Flow Rate Ltrs/Sec

1.29

1.89

2.5

3.18

3.79

5.08

6.29

7.58

9.47

Water Content

Litres

35.44

38.08

44.0

48.28

52,55

61.11

69.66

78.21

91.05

Total Dry

Weight Kg

210

233

256

289

322

388

454

530

644

Gas Rates m3/hr

6.8

10.2

13.6

17.0

20.4

27.2

34.0

40.8

51.0

Cal. Val mj/m3

38.7

38.7

38.7

38.7

38.7

38.7

38.7

38.7

38.7

NH200-NH600 flow and return connections BSP Female Sockets. 

NH800-NH1500 flow and return flanged connections. All flue connections are collars to take Spigot end of standard flue pipe. Gas pressure at inlet all models 11.2 mbar.

 

Home ] Back ]

Copyright © 2007 HOVAL Ltd